Glacier Bay Insulation Test Result Tables |
|
For product photographs and manufacturer's information,
click on the Manufacturer's name shown in the table.
|
|
Radiant Heat (Reflective) Insulations
|
| Manufacturer | Product Name (Note#) | Sample
Thick. |
Claimed
"R" Value |
Actual "R" Value |
Actual
"R" Value Per Inch |
| UQP | "The Insulator" #3200 (1) | 0.50 | N/A | 1.80 | 3.59 |
| UQP | "The Insulator" #3230 (2) | 0.85" | N/A | 2.74 | 3.22 |
| Heat Shield | Super Refrigerator Liner (3) | 1.25" | 30.0 | 4.30 | 3.44 |
| Reflectix | Reflectix (4) | 0.28" | 8.3 to 14.3 | 0.67 | 2.38 |
|
Notes: |
|
Foam Insulations
|
| Manufacturer | Product Name (Note#) | Sample
Thick. |
Claimed
"R" Value |
Actual "R" Value |
Actual
"R" Value Per Inch |
| Dow | Expanded polystyrene (1) | 1.00" | N/A | 3.84 | 3.84 |
| Dow | Extruded polystyrene (2) | 1.00" | 5.0 | 4.92 | 4.92 |
| Celotex | Thermax (3) | 1.00" | 7.2 | 6.35 | 6.35 |
| Fomo | Handi-Foam (4) | 1.00" | 6.67 | 6.64 | 6.64 |
| N/A | Aged "pour-in" foam - dry (5) | .95 | N/A | 3.51 | 3.69 |
| N/A | Aged "pour-in" foam - wet (6) | .95 | N/A | 2.94 | 3.09 |
|
Notes: |
|
Vacuum Panel Insulations |
| See Vacuum
Insulation Panels - General Information for additional
technical information
|
| Manufacturer | Product Name (Note#) | Sample Thick. |
Claimed "R" Value |
Actual "R" Value |
Actual "R" Value Per Inch |
| Glacier Bay | BARRIER 20 (1) | 1.00" | 20.0 | 24.06 | 24.06 |
| VacuPanel | "RParts" vacuum panel (2) | 1.00" | 20.0 | 4.36 to 21.65 | 4.63 to 21.65 |
| VacuPanel | "Technautics" vacuum panel (3) | 1.00" | 40.0 | 9.16 | 9.16 |
|
Notes: |